The formula
Single-phase AC or DC: Vd = 2 × L × I × R × PF
Three-phase AC: Vd = √3 × L × I × R × PF
R = ρ ÷ A (Ω per metre); ρ at 75 °C: copper 2.10 × 10⁻⁸ Ω·m, aluminium 3.45 × 10⁻⁸ Ω·m
% drop = Vd ÷ supply voltage × 100; cable loss = 2I²RL (single-phase)
Worked example
- 10 AWG copper (5.26 mm²), 30 A, 240 V single-phase, 150 ft (45.7 m) one way:
- R = 2.10 × 10⁻⁸ ÷ 5.26 × 10⁻⁶ = 0.00399 Ω/m (1.22 Ω per 1,000 ft).
- Vd = 2 × 45.7 × 30 × 0.00399 = 10.9 V, which is 4.6% of 240 V, leaving 229 V at the load.
- The wire turns 2 × 30² × 0.00399 × 45.7 = 328 W into heat.
What causes voltage drop?
All conductors have some resistance, so when current flows, part of the supply voltage is used up pushing it through the wire. This voltage drop follows Ohm's law: it's the current times the total resistance of the cable. The drop increases with the length of the run and the current, and decreases with a larger conductor. On a single-phase or DC circuit, current flows out on one conductor and back on the other, so the effective length is twice the one-way distance.
How much drop is acceptable?
In the US, the NEC suggests a maximum 3% drop for branch circuits and 5% overall from the service to the furthest outlet. BS 7671 in the UK allows 3% for lighting and 5% for other circuits from the origin of the installation. For a 120 V circuit, 3% is just 3.6 V, so long 120 V runs are especially sensitive. Low-voltage systems such as 12 V solar and RV wiring are even more sensitive: a 0.5 V drop is over 4%, so these often need much larger cables than you might expect.
Effects of excessive drop
When voltage at the load is too low, motors draw more current and run hot, shortening their life; compressors and pumps may struggle to start; LED drivers and electronics can flicker or shut down; and heaters produce less heat. The lost voltage isn't just a performance problem: it's energy wasted as heat in the cable, which you pay for. The calculator shows this power loss, which for long, heavily loaded runs can be hundreds of watts.
Three-phase and power factor
In a balanced three-phase circuit, the line-to-line voltage drop is √3 times the current times the resistance of one conductor, rather than twice. Enter the line-to-line voltage, such as 208, 400 or 480 V. For AC loads with a power factor below 1, such as motors, the resistive drop is reduced by the power factor, but reactance adds some drop that this simplified calculation ignores. That's accurate for smaller cables, but for very large conductors use the impedance values in NEC Chapter 9, Table 9.
Temperature and material
Copper's resistance rises by about 0.4% per °C, so a conductor running at its 75 °C rating has around 20% more resistance than at 20 °C. The calculator uses 75 °C values, which are conservative. Aluminium has about 1.6 times the resistance of copper for the same size, so aluminium runs need larger cables. To pick the smallest wire that meets both the voltage drop and the ampacity requirements, use our wire size calculator.
A low-voltage example
A 12 V, 10 A load at the end of a 6 m run of 4 mm² copper cable drops 2 × 6 × 10 × 0.0052 = 0.63 V, which is 5.2%. Moving to 10 mm² cable cuts the drop to 0.25 V, or 2.1%. This is why battery and solar cables are much thicker than mains cables carrying the same power.
Reducing voltage drop
The options are to use a larger conductor, shorten the run, raise the voltage or reduce the current. Using 240 V instead of 120 V for the same power halves the current and quarters the percentage drop, which is why long runs to workshops and pumps are often 240 V. In solar installations, wiring panels in series raises the voltage and cuts losses. Our solar battery calculator sizes off-grid systems, and the Ohm's law calculator handles the basic relationships.