The formula
Design current = load current × 1.25 for continuous loads (NEC 210.19, 215.2)
Conductor area: d(mm) = 0.127 × 92^((36 − AWG) ÷ 39); A = πd²/4
Resistance R = ρ × length ÷ A, with ρ(copper, 75 °C) ≈ 2.10 × 10⁻⁸ Ω·m
Voltage drop = 2 × L × I × R (single-phase/DC) or √3 × L × I × R (three-phase)
Choose the smallest size whose ampacity ≥ design current and whose drop ≤ the limit
Worked example
- A 30 A, 240 V single-phase load 150 ft away, copper, 3% maximum drop:
- 10 AWG is rated 35 A, but its drop is 2 × 45.7 m × 30 A × 0.00399 Ω/m = 10.9 V, or 4.6%.
- 8 AWG drops 6.9 V (2.9%), so it's the minimum size: upsized from 10 AWG for voltage drop.
Two checks for every wire
Choosing a wire size means passing two separate tests. First, the conductor must carry the current without overheating its insulation: this is its ampacity, set by electrical codes such as the US National Electrical Code (NEC), the Canadian Electrical Code, BS 7671 in the UK and AS/NZS 3008 in Australia. Second, it must deliver enough voltage to the load: every wire has resistance, so some voltage is lost along it. For short runs, ampacity usually decides the size; for long runs, voltage drop often requires a thicker wire than the current alone would need.
Ampacity and the NEC tables
In the US, building wire ampacities come from NEC Table 310.16. The calculator uses the 75 °C column, which applies to most terminations rated 75 °C and to common THHN, THWN-2 and XHHW-2 conductors. Small conductors also have breaker limits under NEC 240.4(D): 14 AWG copper is limited to 15 A, 12 AWG to 20 A and 10 AWG to 30 A. These ratings assume no more than three current-carrying conductors in a raceway and an ambient temperature of 30 °C; more conductors or hotter conditions require derating.
Continuous loads
Loads that run for three hours or more, such as EV chargers, electric water heaters, space heaters and commercial lighting, are continuous loads under the NEC. Their conductors and breakers must be sized for 125% of the load current. A 32 A EV charger therefore needs a circuit rated at least 40 A, typically 8 AWG copper on a 40 A breaker. Tick the continuous load option to apply this factor automatically. Our EV charging calculator shows charging times for different circuit sizes.
Voltage drop limits
The NEC recommends, in informational notes, that branch circuits drop no more than 3% and the combined feeder and branch circuit no more than 5%. Excessive voltage drop makes motors run hot and inefficiently, lights dim and electronics misbehave, and wastes energy as heat in the wire. Voltage drop is proportional to length, so doubling the distance doubles the drop. Long runs to outbuildings, wells, gates and garden lighting are where it matters most. Our voltage drop calculator checks a specific wire.
Copper or aluminium?
Copper has lower resistance and is used for most branch circuits. Aluminium is lighter and cheaper, so it's common for large feeders and service entrances, but it needs to be about two sizes larger for the same ampacity and must be terminated with connectors rated for aluminium (marked AL or AL/CU) to prevent loose, overheating connections. For metric installations, the calculator uses BS 7671 method C (clipped direct) ratings as an indication; installation method, grouping and thermal insulation can reduce these ratings significantly.
Safety first
This calculator gives an estimate for planning and comparing options. Electrical installations must comply with local codes, and in many places work on fixed wiring must be carried out or inspected by a licensed electrician. The correct size also depends on the breaker, the insulation type, the terminal temperature rating, the installation method and derating factors. For the underlying equations, see our Ohm's law calculator, and for sizing a backup supply, the generator size calculator.