The formula
Cooling (ENERGY STAR room chart): e.g. 150–250 ft² → 6,000 BTU/h · 350–400 ft² → 9,000 · 450–550 ft² → 12,000 · 700–1,000 ft² → 18,000
Adjustments: × (ceiling height ÷ 8 ft) · shaded −10% · sunny +10% · +600 BTU/h per person over 2 · +4,000 BTU/h for a kitchen
Heating = floor area × 30–60 BTU/h per ft² (by climate) × insulation factor × (ceiling ÷ 8 ft)
1 ton of cooling = 12,000 BTU/h · 1 kW = 3,412 BTU/h
Worked example
- A 16 × 14 ft (224 sq ft) bedroom has 8 ft ceilings, average sun and insulation and two occupants, in a moderate climate.
- The ENERGY STAR chart gives 6,000 BTU/h for 150–250 sq ft, and no adjustments apply.
- Cooling: 6,000 BTU/h = 0.5 ton = 1.76 kW, so a 6,000 BTU/h window or mini-split unit fits.
- Heating at 45 BTU/h per sq ft for a moderate climate: 224 × 45 = 10,080 BTU/h, about 2.95 kW.
- If the room were very sunny, cooling would rise by 10% to 6,600 BTU/h, which calls for an 8,000 BTU/h unit.
What BTU means
A British thermal unit (BTU) is the energy needed to heat one pound of water by 1 °F. Air conditioner and heater capacities are given in BTU per hour (BTU/h, usually shortened to BTU). Larger systems are rated in tons: one ton is 12,000 BTU/h, the cooling power of melting a ton of ice over a day. Outside North America, capacities are usually quoted in kilowatts: 1 kW equals about 3,412 BTU/h, so a 2.5 kW split system is roughly an 8,500 BTU/h unit. The calculator shows all three units.
Sizing an air conditioner
The starting point is the room area, using the chart published by the US ENERGY STAR programme for room air conditioners: about 20 BTU per square foot for typical rooms, slightly more for small rooms. Then adjust for conditions that add heat. A very sunny room needs about 10% more, a shaded one 10% less. Each extra person adds about 600 BTU/h of body heat, and a kitchen needs about 4,000 BTU/h more for cooking appliances. Rooms with high ceilings have more air to cool, so the calculator scales by ceiling height relative to 8 ft. Poor insulation, single glazing and top-floor rooms under a hot roof also need more capacity.
Why bigger isn't better
An oversized air conditioner cools the room quickly and then switches off before it has removed much moisture from the air. That short-cycling leaves the room cold but clammy, wastes energy and wears out the compressor sooner. An undersized unit runs continuously and may never reach the set temperature on the hottest days. Aim for the recommended size, rounding up to the next standard unit only when you're close to the boundary. Inverter (variable-speed) units are more forgiving, because they can run at low output for long periods.
Sizing a heater
Heating needs depend mainly on how cold it gets outside and how well the room keeps heat in. The calculator uses typical rules of thumb of 30–35 BTU/h per square foot in hot climates, rising to 50–60 in cold ones, adjusted for insulation and ceiling height. For a whole home, a proper heat-loss calculation, which considers wall and window areas, insulation levels and air leakage, is far more accurate; our R-value and heat loss calculator shows how. In the US, HVAC contractors use ACCA Manual J for whole-house sizing.
Heat pumps and cold climates
A heat pump provides both cooling and heating, but its heating output falls as outdoor temperatures drop. When sizing for heating in cold climates, check the manufacturer's capacity at your design temperature, often listed at 17 °F and 5 °F (−8 °C and −15 °C). Cold-climate models keep much more of their output in freezing weather. In mild and moderate climates, a heat pump sized for the cooling load usually covers most of the heating as well, with a backup heater for the coldest days.
Choosing a system
- Window and portable units are cheap and easy to install but noisy. Portable units are the least efficient, especially single-hose models.
- Ductless mini-splits are quiet and efficient, and most work as heat pumps for heating too.
- Central air and heat pumps serve the whole house through ducts.
Compare efficiency using SEER2 or EER ratings in the US, or SCOP and energy labels in Europe and the UK: higher numbers cost less to run. Check running costs with our appliance electricity cost calculator, and plan the airflow for ducted systems with the CFM and duct size calculator.