The formula
Superheat = suction line temperature − evaporator saturation (dew-point) temperature
Subcooling = condenser saturation (bubble-point) temperature − liquid line temperature
Saturation temperatures come from the refrigerant's pressure–temperature (PT) table at the measured pressures
Fixed-orifice target superheat (°F) ≈ (3 × indoor wet-bulb − 80 − outdoor dry-bulb) ÷ 2
Worked example
- An R-410A system reads 118 psig at the suction service valve, with a suction line temperature of 52 °F.
- At 118 psig, R-410A saturates at 39.8 °F, so superheat = 52 − 39.8 = 12.2 °F.
- The liquid line reads 365 psig and 100 °F. At 365 psig, R-410A condenses at 109.7 °F, so subcooling = 109.7 − 100 = 9.7 °F.
- With a 63 °F indoor wet-bulb and 85 °F outdoors, the fixed-orifice target superheat = (3 × 63 − 80 − 85) ÷ 2 = 12 °F.
- Both readings are in a typical range, suggesting the charge is about right.
What superheat and subcooling tell you
In an air conditioner or heat pump, refrigerant boils in the evaporator and condenses in the condenser. While it's changing state, its temperature is fixed by its pressure, which is what a pressure–temperature (PT) chart shows. Superheat is how far the vapour leaving the evaporator has been heated above its boiling point. It confirms that all the liquid has boiled off before it reaches the compressor. Subcooling is how far the liquid leaving the condenser has been cooled below its condensing temperature, showing that the condenser is full of liquid and the metering device will be fed properly. Together they're the main tools technicians use to check refrigerant charge.
Taking the measurements
Measure suction pressure at the suction service valve and the suction line temperature 4–6 in (10–15 cm) from the valve with a clamp thermometer, insulated from ambient air. Measure liquid pressure at the liquid service valve and the liquid line temperature nearby. Let the system run for at least 10–15 minutes with clean filters, coils and correct indoor airflow, because poor airflow gives misleading readings. Digital manifold gauges calculate superheat and subcooling automatically, and this calculator does the same from your readings.
Which reading to charge by
Systems with a fixed orifice or piston metering device are charged by superheat. The target depends on indoor and outdoor conditions, typically from a chart on the unit or the formula in this calculator, often 8–20 °F at normal conditions. Systems with a TXV or EEV (thermostatic or electronic expansion valve) control superheat themselves, so they're charged by subcooling, usually 8–12 °F (4–7 K) or the value on the unit's rating plate. Always follow the manufacturer's charging instructions where available.
Reading the results
- High superheat, low subcooling: usually undercharged, possibly from a leak.
- Low superheat, high subcooling: usually overcharged.
- High superheat, high subcooling: often a restriction, such as a blocked filter drier or a faulty TXV.
- Low superheat, low subcooling: often low indoor airflow, a dirty evaporator coil or a metering problem.
Very low superheat risks liquid reaching the compressor, which can destroy it; very high superheat makes it run hot. Diagnose carefully, because adding or removing refrigerant to fix an airflow problem creates new faults.
Common mistakes
The most common errors are measuring line temperatures with poor contact or in the sun, taking readings before the system has stabilised, and charging when indoor airflow or coil cleanliness is wrong. Using the wrong refrigerant's PT chart is another, especially with similar-looking gauges. Remember that gauges read gauge pressure (psig or bar g), not absolute pressure. Outdoor temperatures below about 60–65 °F (15–18 °C) make charging by superheat unreliable, so many manufacturers specify weighing in the charge instead.
Refrigerants and safety
R-22 has been phased out of production in the US, EU and many other countries because it damages the ozone layer. R-410A is being phased down under the AIM Act and EU F-gas rules, and new US residential systems from 2025 mostly use R-454B or R-32, which have lower global-warming potential but are mildly flammable (class A2L). Zeotropic blends such as R-407C, R-404A and R-454B boil over a temperature range, so superheat uses the dew-point temperature and subcooling the bubble-point temperature, as this calculator does. Only certified technicians (EPA Section 608 in the US, F-gas certification in the UK and EU) may work on refrigerant circuits. The PT values here are computed from published equations of state and are approximate; use the manufacturer's PT chart for final charging. For sizing equipment, see our BTU calculator and duct size calculator.