The formula
R-value of insulation = R per inch × thickness (RSI = thickness ÷ λ in metric)
Total R = insulation R + other layers + air films (R-0.85)
U = 1 ÷ total R
Heat loss Q = area × U × (inside − outside temperature)
Annual heat lost = area × U × heating degree days × 24 h
Annual cost = annual kWh ÷ heating efficiency × price per kWh
US: Q in BTU/h with area in ft², ΔT in °F · Metric: Q in W with area in m², ΔT in °C, U in W/m²·K
Worked example
- A 1,000 sq ft wall has 3.5 in fiberglass batts (R-3.2 per inch) and other layers worth R-2.
- Insulation R = 3.2 × 3.5 = 11.2, so total R = 11.2 + 2 + 0.85 = 14.05 and U = 1 ÷ 14.05 = 0.071.
- At 68 °F inside and 10 °F outside, heat loss = 1,000 × 0.071 × 58 = 4,128 BTU/h (1,210 W).
- With 5,000 °F heating degree days: 1,000 × 0.071 × 5,000 × 24 = 8.54 million BTU = 2,503 kWh a year.
- With a 95% efficient system at $0.15 per kWh, that's $395 a year.
- Adding another 3.5 in of batt insulation would save about $175 a year.
R-values and U-values
An R-value measures how well a material resists heat flow: the higher the number, the better it insulates. R-values of layers in a wall, roof or floor simply add together. A U-value is the opposite: the rate of heat flow through the whole assembly, equal to 1 divided by the total R-value. Lower U-values are better. In the US, R-values are given in ft²·°F·h/BTU. Elsewhere, insulation is rated with RSI in m²·K/W, and building assemblies with U-values in W/m²·K. To convert, R-value (US) = RSI × 5.678. A US R-13 wall is RSI 2.29.
Insulation materials compared
- Fiberglass and mineral wool batts: about R-3.1 to R-4.2 per inch, cheap and easy to fit between studs. Mineral wool is also fire-resistant and good for sound.
- Blown cellulose: about R-3.5 to R-3.8 per inch, good for attics and filling irregular spaces.
- EPS and XPS foam board: R-4 and R-5 per inch, moisture-resistant, used under slabs and on foundations.
- Polyiso (PIR) board: about R-6 per inch, the highest of common boards, though it performs less well in very cold weather.
- Spray foam: open-cell about R-3.6 per inch; closed-cell about R-6.5 per inch, which also acts as an air and vapour barrier.
Heat loss at the design temperature
Heat loss at a design outdoor temperature, the cold winter temperature used for sizing heating systems (often the 99% design temperature, which is exceeded only 1% of hours), tells you how much heating capacity you need. Add the heat loss through all the walls, windows, roof and floor, plus air leakage, to get the whole-house load. Windows usually lose far more heat per square foot than insulated walls: a double-glazed window might be U-0.30 to U-0.50 (R-2 to R-3), compared with U-0.07 or better for an insulated wall.
Annual energy and cost
Heating degree days (HDD) measure how cold a climate is over a whole year: the sum, for every day, of how far the average temperature falls below a base temperature (65 °F in the US, 15.5–18 °C elsewhere). Multiplying the U-value by area, HDD and 24 hours gives the annual heat loss through that surface. Divide by your heating system's efficiency and multiply by the energy price to get the annual cost. Gas boilers and furnaces are typically 80–98% efficient, electric resistance heating 100%, and heat pumps 250–400% (a seasonal COP of 2.5–4). One therm of natural gas is 29.3 kWh.
Air leakage
Insulation is only half the story: warm air escaping through gaps around windows, doors, pipes, wiring and loft hatches can account for a quarter or more of a home's heat loss. Blower-door tests measure air leakage, often expressed as air changes per hour at 50 pascals (ACH50); typical older homes leak at 7–15 ACH50, while very efficient homes achieve 1–3. Sealing gaps with caulk, foam and weatherstripping is one of the cheapest efficiency upgrades. Tighter homes need controlled ventilation, such as extract fans or heat-recovery ventilation, to keep the air healthy.
Code requirements and payback
Building codes set minimum insulation levels. The 2021 US International Energy Conservation Code requires R-20 cavity insulation or R-13 plus continuous insulation in walls for most of the country, and R-49 to R-60 in attics. UK Building Regulations require new walls to achieve about U-0.18 to U-0.26 W/m²·K. Adding insulation always reduces heat loss, but the savings fall with each extra inch, so the first few inches pay back fastest. Thermal bridging through studs, joists and fixings lowers the effective R-value of framed assemblies, which is why continuous exterior insulation is increasingly common. Use the result to size heating with our BTU calculator or design underfloor heating with the radiant floor heating calculator, and burn wood more efficiently with the firewood calculator.