CFM & Duct Size Calculator

Work out the airflow (CFM) a room or system needs and size round or rectangular ducts with the equal-friction method.

Updated · Free · Runs in your browser

Units
Airflow from
BTU/h
CFM/ton

350–400 CFM per ton is typical; lower in humid climates.

in. w.g./100 ft

0.06–0.10 is typical for residential supply ducts.

in
Round duct size —
Airflow —
Airflow (metric) —
Air velocity —
Equivalent rectangular duct —
Friction rate —
    Was this calculator helpful?

    The formula

    Airflow:
    from cooling load: CFM = (BTU/h ÷ 12,000) × CFM per ton (typically 400)
    from air changes: CFM = room volume (ft³) × ACH ÷ 60
    
    Round duct (equal friction, galvanised steel): friction (in. w.g./100 ft) = 0.109136 × CFM^1.9 ÷ D^5.02
    so D (in) = (0.109136 × CFM^1.9 ÷ friction)^(1/5.02)
    Velocity (ft/min) = CFM ÷ duct area (ft²)
    Rectangular equivalent: De = 1.30 × (a × b)^0.625 ÷ (a + b)^0.25

    Worked example

    1. A 2-ton (24,000 BTU/h) system needs 400 CFM per ton.
    2. Airflow = 24,000 ÷ 12,000 × 400 = 800 CFM.
    3. At a friction rate of 0.08 in. w.g. per 100 ft: D = (0.109136 × 800^1.9 ÷ 0.08)^(1/5.02) = 13.4 in.
    4. The next standard round size is 14 in, with an area of 1.07 sq ft, so velocity = 800 ÷ 1.07 = 748 ft/min.
    5. An 8 in deep rectangular duct with the same friction would need to be 20 in wide (20 × 8 in).
    6. In metric: 378 L/s, 1,359 m³/h at 0.65 Pa/m.

    How much airflow do you need?

    For a central air conditioner or heat pump, the standard design airflow is about 400 cubic feet per minute (CFM) per ton of cooling, or roughly 54 L/s per kW. In humid climates, systems are often set to 350 CFM per ton so the coil runs colder and removes more moisture; in dry climates, up to 450 CFM per ton can improve efficiency. For ventilation and exhaust, airflow is usually based on air changes per hour (ACH): how many times the room's full volume of air is replaced each hour. Typical values are 4–6 ACH for living spaces, 6–10 for bathrooms, 7–15 for kitchens and higher for workshops and garages.

    The equal friction method

    Most residential and light commercial duct systems are designed with the equal friction method: every section of duct is sized so that air loses the same pressure per 100 ft (or per metre) of length. The friction rate depends on the pressure the fan can supply and the total effective length of the longest run, including fittings. Residential systems are typically designed at 0.06–0.10 in. w.g. per 100 ft. A lower friction rate means bigger, quieter ducts and less fan energy; a higher rate means smaller, cheaper ducts but more noise. This calculator uses the ASHRAE friction relationship for round galvanised steel duct, the basis of the familiar cardboard ductulator.

    Round and rectangular ducts

    Round duct is the most efficient shape, with the least surface area and friction for a given airflow. Rectangular duct is used where space is tight, such as between joists or above ceilings. The calculator finds a rectangular size with the same friction as the round duct, using the equivalent-diameter formula from ASHRAE. Keep the aspect ratio (width to height) below about 4:1 where possible, because flat, wide ducts have much higher friction and cost more in metal. Flexible duct has more friction than metal duct, especially when it isn't pulled tight, so size flex runs up one size or design at a lower friction rate.

    Velocity and noise

    Air velocity affects noise as well as pressure loss. Typical design limits for homes are about 700–900 ft/min (3.5–4.5 m/s) in main trunks and 500–700 ft/min (2.5–3.5 m/s) in branch ducts, with lower velocities near grilles in bedrooms and offices. Commercial systems can run faster in main ducts in plant rooms and ceiling voids. If the calculated velocity is high, choose the next size up. Undersized ducts are one of the most common causes of noisy, inefficient HVAC systems and of rooms that never get enough air.

    Return air

    Supply ducts get most of the attention, but return ducts matter just as much. A system needs roughly the same airflow coming back to the air handler as going out, and undersized or missing returns are a common cause of high static pressure, noisy grilles and rooms that don't heat or cool properly. Size return ducts with the same method, usually at a slightly lower friction rate, and make sure bedrooms with closed doors have a return path such as a jumper duct or transfer grille.

    Designing a whole system

    For a complete design, start with a room-by-room load calculation such as ACCA Manual J in the US, which gives the airflow each room needs. Then use Manual D or a similar method to work out the available friction rate from the fan's external static pressure and the total effective length of the longest run, and size each branch and trunk in turn. Leaky ducts can waste 20–30% of the airflow, so seal joints with mastic or foil tape and insulate ducts outside the heated space. Size the equipment first with our BTU calculator and estimate heat loss through walls and roofs with the R-value and heat loss calculator.

    Frequently asked questions

    How many CFM per ton of air conditioning?
    About 400 CFM per ton for most systems, within a range of roughly 350–450 depending on climate and equipment.
    What size duct do I need for 400 CFM?
    At a typical 0.08 in. w.g. per 100 ft friction rate, about 10.5 in, so a 10 or 12 in round duct, or roughly 14 × 8 in rectangular.
    What size duct for 100 CFM?
    About 6 in round at a typical residential friction rate, which is why 6 in branch ducts are so common for bedrooms.
    What is a good duct velocity?
    700–900 ft/min (3.5–4.5 m/s) in residential trunk ducts and 500–700 ft/min (2.5–3.5 m/s) in branches. Higher velocities cause noise.
    How do I calculate CFM for a room?
    Multiply the room volume (length × width × height in feet) by the air changes per hour you need, then divide by 60. A 15 × 12 × 8 ft room at 6 ACH needs 144 CFM.