Radiant Floor Heating Pipe Calculator

Estimate PEX tubing length, number of loops, loop length, heat output per area and flow rate for hydronic underfloor heating.

Updated · Free · Runs in your browser

Units
ft²

Exclude areas under kitchen cabinets, baths and fixed furniture.

ft
BTU/h

From a heat-loss calculation.

°F
Total tubing —
Number of loops —
Length per loop —
Tubing per area —
Required heat output —
Water flow rate —
    Was this calculator helpful?

    The formula

    Tubing in the floor = heated area ÷ tube spacing
    Loops = ceil(floor tubing ÷ (maximum loop length − 2 × distance to manifold))
    Total tubing = floor tubing + loops × 2 × distance to manifold
    Heat output needed = room heat loss ÷ heated area
    Flow rate (US): GPM = BTU/h ÷ (500 × ΔT°F)
    Flow rate (metric): L/min = W ÷ (4,186 × ΔT°C) × 60
    
    Tubing per ft²: 2 ft at 6 in, 1.33 ft at 9 in, 1 ft at 12 in

    Worked example

    1. A 400 sq ft room has a heat loss of 10,000 BTU/h and will use ½ in PEX at 9 in centres, with the manifold 15 ft away.
    2. Tubing in the floor = 400 ÷ 0.75 ft = 533 ft.
    3. With a maximum loop length of 300 ft, each loop can have 300 − 2 × 15 = 270 ft in the floor, so 533 ÷ 270 = 1.98, or 2 loops.
    4. Total tubing = 533 + 2 × 2 × 15 = 593 ft, about 297 ft per loop.
    5. The floor must deliver 10,000 ÷ 400 = 25 BTU/h per sq ft (79 W/m²).
    6. With a 15 °F temperature drop, the flow is 10,000 ÷ (500 × 15) = 1.33 gpm, or 0.67 gpm per loop.

    How radiant floor heating works

    Hydronic underfloor heating circulates warm water through loops of plastic tubing embedded in or under the floor. The whole floor becomes a large, low-temperature radiator that heats people and objects directly, giving even warmth without draughts or hot spots. Because the water only needs to be 85–120 °F (30–50 °C) rather than the 140–180 °F (60–80 °C) needed by radiators, underfloor heating works very well with condensing boilers and especially heat pumps, which are most efficient at low flow temperatures.

    Tube spacing

    Spacing determines how much tubing goes into each square foot and how much heat the floor can deliver. Tighter spacing gives more output at a lower water temperature and a more even floor surface temperature. Common choices are 6 in (150 mm) for high heat-loss areas, bathrooms and along exterior walls; 9 in (200–225 mm) for general living spaces in well-insulated homes; and 12 in (300 mm) for well-insulated rooms with low heat loss. Many designers use tighter spacing in a perimeter band along cold exterior walls and windows. At 9 in spacing, you need about 1.33 ft of tube per square foot.

    Loop length and manifolds

    Each loop runs from a supply manifold, through the floor and back to a return manifold. Long loops have high pressure drops, need bigger pumps and deliver uneven heat, so manufacturers set maximum lengths: typically about 250 ft for ⅜ in PEX, 300 ft for ½ in, 400 ft for ⅝ in and 500 ft for ¾ in, or about 80–120 m for 12–20 mm pipe. Keep loops in the same zone at similar lengths, within about 10%, so they balance well, and include the leader lengths from the manifold to the room. Each loop has its own valve and flow meter on the manifold for balancing.

    How much heat can a floor deliver?

    Comfortable floor surface temperatures limit the output. Standards such as EN 1264 recommend a maximum floor surface temperature of about 29 °C (84 °F) in occupied areas and 33 °C (91 °F) in bathrooms and edge zones. With a room at 20–21 °C, that limits output to about 100 W/m² (32 BTU/h per sq ft). Most well-insulated modern homes need 30–70 W/m² (10–22 BTU/h per sq ft). If a room needs more, improve its insulation, add a perimeter band of tighter tubing, or supplement with a radiator or fan coil. Floor coverings matter too: thick carpet and underlay can halve output compared with tile or stone.

    Installation methods

    Tubing can be installed in several ways. In new concrete slabs, it's tied to the reinforcement or clipped to insulation boards and buried in the concrete. In screed systems, it's laid on insulation and covered with 50–75 mm of sand–cement or liquid screed. In timber floors, it sits in grooved aluminium spreader plates between or above joists, or in low-profile overlay panels. Concrete systems respond slowly but store heat, while dry systems with aluminium plates warm up faster and suit renovations where floor height is limited.

    Flow rate and temperature drop

    Water cools as it gives up heat, and the difference between supply and return temperatures (ΔT) is typically designed at 10–20 °F (5–10 °C). A smaller ΔT needs more flow but keeps the floor temperature more even. The calculator gives the total flow and flow per loop, which you can use to size the circulator pump and manifold. You'll need the room's heat loss for an accurate design: use our R-value and heat loss calculator for walls, roofs and floors, and our BTU calculator for a quick estimate. Underfloor heating also needs insulation beneath the tubing, at least R-5 to R-10 (25–50 mm or more of rigid foam), so heat goes up into the room rather than down into the ground.

    Frequently asked questions

    How much PEX do I need for radiant floor heat?
    About 1.33 ft per sq ft at 9 in spacing, 2 ft per sq ft at 6 in and 1 ft per sq ft at 12 in, plus the leader runs to and from the manifold for each loop.
    How long can a radiant heat loop be?
    Typically up to 250 ft for ⅜ in PEX, 300 ft for ½ in, 400 ft for ⅝ in and 500 ft for ¾ in. In metric, about 80 m for 12 mm, 100 m for 16 mm and 120 m for 20 mm pipe.
    What spacing should radiant floor tubing be?
    9 in (about 200 mm) for most well-insulated living spaces, 6 in (150 mm) for bathrooms and high heat-loss areas, and 12 in (300 mm) where heat loss is low.
    How many BTU per square foot does radiant floor heating produce?
    Usually 15–30 BTU/h per sq ft (50–95 W/m²), with a practical maximum of about 32 BTU/h per sq ft (100 W/m²) before the floor feels too warm.
    What water temperature does underfloor heating need?
    Usually 85–120 °F (30–50 °C) supply water, depending on the heat loss, tube spacing and floor covering. Lower temperatures make heat pumps and condensing boilers more efficient.