The formula
Manning's equation (SI): V = (1/n) × R^(2/3) × S^(1/2); Q = V × A
US units: V = (1.486/n) × R^(2/3) × S^(1/2) (ft/s)
R = hydraulic radius = flow area ÷ wetted perimeter (D/4 for a full pipe)
S = slope (ft/ft or m/m); n = Manning roughness coefficient
Part-full circular pipe: θ = 2 × arccos(1 − 2y/D); A = D²(θ − sin θ)/8; P = Dθ/2
Full-pipe diameter for flow Q: D = (Q × n × 4^(5/3) ÷ (π × √S))^(3/8)
Worked example
- An 18 in concrete pipe (n = 0.013) is laid at a 1% slope and flows full.
- D = 0.457 m, so A = π × 0.457² ÷ 4 = 0.164 m² (1.77 sq ft) and R = D ÷ 4 = 0.114 m.
- V = (1 ÷ 0.013) × 0.114^(2/3) × 0.01^(1/2) = 76.9 × 0.236 × 0.1 = 1.82 m/s (5.97 ft/s).
- Q = 1.82 × 0.164 = 0.299 m³/s, or 10.5 cu ft/s (about 4,735 US gpm).
- A corrugated metal pipe (n = 0.024) of the same size would carry only about 5.7 cu ft/s.
What Manning's equation does
Manning's equation, published by the Irish engineer Robert Manning in 1889, is the standard way to estimate gravity flow in open channels and pipes that aren't under pressure, such as culverts, storm drains, sewers, ditches and gutters. It links the flow velocity to the channel's slope, its roughness and its hydraulic radius, the flow area divided by the wetted perimeter. Steeper, smoother and larger channels carry water faster. Multiply the velocity by the flow area to get the flow rate. The equation is empirical, but it's been validated across a huge range of conditions and is used in design manuals worldwide.
Choosing Manning's n
The roughness coefficient n has a large effect on capacity. Typical values are 0.009–0.011 for PVC, 0.012 for smooth-walled HDPE, 0.013 for concrete pipe, 0.020–0.024 for corrugated plastic and corrugated metal, and 0.022–0.035 or more for earth and grassed channels. Because flow is inversely proportional to n, a corrugated metal pipe carries only about 55% of the flow of a concrete pipe of the same size and slope. Designers often choose conservative values to allow for ageing, debris and joints.
Full and partly full pipes
Storm drains are usually designed to flow full or nearly full at the design storm. Surprisingly, a circular pipe carries its maximum flow at about 93–94% of its depth, not when completely full, because the last few percent of depth adds more wetted perimeter (friction) than flow area. Velocity peaks at about 81% depth. Use the depth slider to model part-full conditions, for example for sewers, which are often designed to run no more than half to three-quarters full.
Culvert design considerations
Real culverts under roads and driveways are often controlled by their inlet or outlet rather than by pipe friction alone, especially when short, steep or submerged. Design manuals such as the US Federal Highway Administration's HDS-5 check inlet control, outlet control and headwater depth. Manning's equation gives the barrel capacity, which is the first step. Also consider minimum velocities of about 2–3 ft/s (0.6–0.9 m/s) so sediment doesn't settle, maximum velocities to avoid erosion at the outlet, and minimum cover over the pipe for traffic loads. Local authorities usually specify the design storm, such as the 10-year or 25-year event.
Maintenance of culverts and drains
Even a correctly sized culvert can fail if it's blocked. Debris, sediment and vegetation at the inlet can reduce capacity dramatically, leading to flooding over roads and erosion around the pipe. Inspect culverts after major storms and at least once a year, clear trash racks and inlets, and check outlets for scour. Pipes with a slope that's too flat collect sediment, while steep pipes may need energy dissipation at the outlet. Where wildlife needs to pass, larger box culverts or bridges with natural streambeds are increasingly required.
Estimating the design flow
The flow a culvert must carry depends on the catchment area, rainfall intensity and ground surface. For small catchments, engineers often use the Rational Method: Q = C × i × A, where C is a runoff coefficient (about 0.9 for roofs and paving, 0.1–0.3 for lawns), i is rainfall intensity and A is the area. Enter a design flow in the optional field to get the minimum full-flow diameter, then choose the next standard pipe size. For roof drainage, our gutter and sump pump calculator covers smaller flows, and the slope calculator converts pipe falls into percentages. For pressurised water pipes, use the pipe friction loss calculator instead.