Pipe Friction Loss & Pump Head Calculator

Calculate friction loss in water pipes with the Hazen–Williams equation, then add elevation and outlet pressure for total dynamic head and pump power.

Updated · Free · Runs in your browser

Units
gpm
in

Sch 40 PVC: 1 in ≈ 1.03 in, 1½ in ≈ 1.61 in, 2 in ≈ 2.07 in.

ft
%
ft
psi

e.g. sprinklers often need 30–50 psi.

%
Total dynamic head —
Friction loss —
Friction gradient —
Water velocity —
Pump pressure needed —
Pump power —
    Was this calculator helpful?

    The formula

    Hazen–Williams (US units):
    hf per 100 ft = 0.2083 × (100 ÷ C)^1.852 × Q^1.852 ÷ d^4.8655
    Q = flow (gpm), d = internal diameter (in), hf in feet of water
    Pressure loss (psi) = head (ft) × 0.433
    Velocity (ft/s) = 0.4085 × Q ÷ d²
    
    Total dynamic head = friction + elevation gain + outlet pressure head
    Water horsepower = gpm × TDH(ft) ÷ 3,960; shaft power = water hp ÷ pump efficiency

    Worked example

    1. Water flows at 20 gpm through 200 ft of 1½ in Schedule 40 PVC (internal diameter 1.61 in, C = 150), with 20% added for fittings, so the equivalent length is 240 ft.
    2. Friction = 0.2083 × (100 ÷ 150)^1.852 × 20^1.852 ÷ 1.61^4.8655 = 2.5 ft per 100 ft (1.08 psi per 100 ft).
    3. Over 240 ft: 6.0 ft of head, or 2.59 psi. Velocity = 0.4085 × 20 ÷ 1.61² = 3.15 ft/s.
    4. The water must rise 30 ft and arrive at 30 psi (69.3 ft of head), so TDH = 6.0 + 30 + 69.3 = 105.3 ft.
    5. Water horsepower = 20 × 105.3 ÷ 3,960 = 0.53 hp; at 60% pump efficiency the pump needs 0.89 hp (0.66 kW).
    6. In 1 in pipe, the same flow would lose 22.7 psi to friction at 7.7 ft/s.

    Why pressure drops in a pipe

    As water flows through a pipe, friction between the water and the pipe wall, and turbulence within the flow, use up energy. That loss appears as a drop in pressure along the pipe, called friction loss or head loss. It rises steeply with flow rate, roughly with the square of the velocity, and falls sharply with diameter: doubling the pipe diameter cuts friction loss by a factor of about 30 for the same flow. That's why a pipe that's one size too small can make a shower feel weak, an irrigation zone underperform or a pump struggle.

    The Hazen–Williams equation

    The Hazen–Williams formula is the standard method for water at normal temperatures in plumbing, irrigation, fire sprinkler and water supply systems. It uses a roughness coefficient C: about 150 for plastic pipes such as PVC, PEX and HDPE, 140 for copper, 120–130 for new steel and iron, and 100 or less for old, corroded pipes. For other fluids, very high velocities or very small pipes, engineers use the more general Darcy–Weisbach equation. Always use the pipe's internal diameter, which differs from its nominal size: 1 in Schedule 40 PVC is 1.03 in inside, while 1 in Schedule 80 is 0.94 in.

    Fittings and valves

    Every elbow, tee, valve and meter adds extra friction, usually expressed as an equivalent length of straight pipe. A standard 90° elbow might add 2–5 ft, a tee with flow through the side 5–10 ft, and a check valve 10–20 ft, depending on size. For a quick estimate, add 10–20% to the straight pipe length for typical domestic and irrigation layouts, and more for systems with many fittings. For detailed designs, add up the equivalent lengths of each fitting from manufacturers' tables.

    Total dynamic head and pump sizing

    A pump must overcome three things: friction loss, the height the water must be lifted (static head) and the pressure needed at the outlet, such as 30–50 psi for sprinklers or a minimum pressure at a tap. Together these make up the total dynamic head (TDH), usually given in feet or metres of water: 1 psi equals 2.31 ft of head and 1 bar equals 10.2 m. With the flow rate and TDH, you can choose a pump whose curve passes through that duty point, ideally near its best efficiency point. The calculator also estimates the shaft power needed, based on the pump efficiency you enter; small pumps are typically 40–65% efficient.

    Choosing a pipe size

    When you're designing a new system, start with the flow you need at the most demanding outlet and pick a pipe size that keeps velocity below about 5 ft/s. Then check the friction loss over the longest run. If the pressure at the outlet would drop below what fixtures or sprinklers need, go up a size or shorten the run. For domestic water, many designers aim for no more than 4–8 psi of friction loss from the meter to the furthest fixture. A slightly larger pipe usually costs little more but saves pump energy for decades.

    Keep water velocity below about 5 ft/s (1.5 m/s) in most domestic and irrigation pipework, and below 8 ft/s (2.4 m/s) in any case. Faster flow is noisy, causes water hammer when valves close and can erode copper pipe. If your velocity is too high, use the next pipe size up: it usually saves energy over the life of the system too. For gravity drains and culverts, which flow without pressure, use our Manning's equation calculator. To size sump pumps for drainage, try the gutter and sump pump calculator, and for pool pumps, the pool volume calculator gives the turnover flow rate.

    Frequently asked questions

    How do I calculate friction loss in a pipe?
    Use the Hazen–Williams equation with the flow rate, internal diameter, pipe length and the C factor for the material. The calculator does this and converts the result to psi, feet of head, bar or kPa.
    What is the C factor for PVC pipe?
    150 for new PVC, PEX, CPVC and HDPE. Copper is usually taken as 140 and new steel as 120.
    How many feet of head is 1 psi?
    1 psi equals 2.31 ft of water head. 1 bar equals about 10.2 m of head.
    What is total dynamic head?
    The total pressure a pump must provide: friction losses plus the vertical lift plus the pressure required at the outlet, expressed in feet or metres of water.
    What water velocity is too fast?
    Above about 5 ft/s (1.5 m/s) is higher than recommended for most plumbing and irrigation, and above 8 ft/s (2.4 m/s) risks noise, water hammer and erosion.